363-205-401 Power Up:
Issue 7, March 1997 Page 1 of 10
DLP-507
Perform Battery Charger Test
SUMMARY:
Unseat all
BATTERY CHARGER
s. Reseat a
BATTERY CHARGER
.
Verify that
BAT DISCHG
indicator goes off and remains off,
HIGH RATE CHG/ON
indicator lights, and
OPEN BAT
indicator is off. Unseat
BATTERY CHARGER
and
repeat for additional
BATTERY CHARGER
s. Reseat all
BATTERY CHARGER
s.
Remove AC power from system. Measure 42 to 56 V DC at
LDU
(
48L/GND
).
Restore AC power. Remove either
+BAT
or
BAT
fuse on battery shelf. Verify that
OPEN BAT
indicator lights and
HIGH RATE CHG/ON
indicator is off. Replace
+BAT
or
BAT
fuse. Verify that
OPEN BAT
indicator goes off. Repeat for other battery
strings. Press
HIGH RATE CHG/ACTIVATE
button on
BATTERY CHARGER
and
verify that
BAT DISCHG
indicator goes off and
HIGH RATE CHG/ON
indicator lights.
Repeat for other
BATTERY CHARGER
s. Verify that
HIGH RATE CHG/ON
indicator(s) goes off within 24 hours.
1.
NOTE:
Throughout this procedure the
BAT DISCHG
and the
HIGH RATE
CHG/ON
indicators on
BATTERY CHARGER
will light at steps indicated.
The amount of time these indicators are lighted is a function of charge
state of batteries. However, these indicators should at least light
momentarily at appropriate steps.
Verify that all
336A RECTIFIER
s are seated and all
BATTERY CHARGER
s
are unseated. Reseat one of the
BATTERY CHARGER
s while observing indi-
cators on
BATTERY CHARGER
faceplate.
Response:
BAT DISCHG
indicator will light and remain lighted for a
period of time determined by charge state of batteries.
If
BAT DISCHG
indicator remains lighted for more than 4
minutes,
BCU PMN
(or
P/M
) and
ADU NE
indicators will also
light.
When
BAT DISCHG
indicator goes off, the
HIGH RATE
CHG/ON
indicator will light and, if
BCU PMN
(or
P/M
) and
ADU NE
indicators are lighted, they will go off after 4 min-
utes.
The
HIGH RATE CHG/ON
indicator will go off after a period
of time determined by charge state of batteries.