363-205-401 RT Turn Up:
Issue 7, March 1997 Page 1 of 4
DLP-523
Install Alarm Display Unit in FP303 Optioned for
Preservice and Unequipped
1. Get one alarm display unit (
ADU
), as required, and inspect for possible dam-
age.
2. On
AUB27( )
option switch
S1
(Table A and Figure 1), use an orange stick
(KS-6320, L1) or equivalent and set switch positions as follows:
•
1
- Toward
PL
if equipping system with protection switching. Otherwise,
toward
NPL
. (See work order.)
•
2
- Toward
4
.
•
3
- Toward
ABP
.
•
4
- Toward
CDP
.
•
5
- Toward
ABU
.
•
6
- Toward
CDU
.
•
7
- Toward
1MJ
if
MISC1
is to report a major alarm or toward
1MN
if
MISC1
is to report a minor alarm. (See work order.)
•
8
- Toward
2MJ
if
MISC2
is to report a major alarm or toward
2MN
if
MISC2
is to report a minor alarm. (See work order.)