Conversions: DLP-508 363-205-401
Page 4 of 4 Issue 7, March 1997
12. Are switch settings on option switch correct?
If
YES,
then continue with Step
13.
If
NO,
then proceed to Step
14.
13. Get another
ADU
and set switches on option switch
S1
according to work
order and Step
3
.
14.
!
CAUTION:
Incorrectly set ADU option switches may result in immediate or future
loss of service or may introduce errors into the digital bitstream.
Insert
ADU
into
ADU
slot in bank being equipped.
Response: After approximately 20 seconds,
ADU
and
BCU FAIL
indica-
tors go off.
15. After approximately 20 seconds, do
ADU
and
BCU FAIL
indicators go off?
If
YES,
then
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
If
NO,
then continue with Step
16.
16. Correct setting of switches on option switch and repeat from Step
6.