4.3. Installation Recommendations
In order to obtain a full fastness against electromagnetic noise, it is
recommended to observe following principles:
- do not supply the controller from the network in the proximity
of devices generating high pulse noises and do not apply common
earthing circuits,
- apply network lters,
- wires leading measuring signals should be twisted in pairs,
and for resistance sensors in 3-wire connection, twisted of wires