DMX Power Supply 3 x 96 watt - Installation Instructions
Models PSDMX-3X96-24
Please read all instructions prior to installation and keep for future reference!
This class 2 power supply is to be installed by a qualified electrician in accordance with the National Electrical
Code (NEC) and local building codes. The power supply must be installed in a well ventilated area and free from
explosive gases and vapors. Proper operation requires the free flow of air. Power supply is well suited for LED or
resistive loads at or below their maximum output rating per circuit. Suitable For Damp Location.
WARNING! Risk of Fire or Electric Shock, Do Not Interconnect Output Terminal.
*LUMINII RESERVES THE RIGHTS TO CHANGE SPECIFICATIONS WITHOUT NOTICE
7777 N . Merrimac Ave
Niles, IL 60714
T 224.333.6033
F 224.757.7557
info@luminii.com
www.luminii.com
Page 1 of 3
PLENUM FOR
SUCH USE IN
ACCORDANCE
WITH UL2043
Connect the white (neutral) & black (hot) power
supply wires to the white & black power wires
(120-277VAC). Followed by connecting the ground
wires in accordance with local electrical codes.
terminal block intended wire size
solid or stranded : 28 - 12 AWG
strip length : 0.31 - 0.35
3
4
Before installing, check the label and ensure the power
supply has the proper input voltage, output voltage, and
wattage for the job. Check the wire markings to ensure
they match the wiring diagram below. Refer to table above
for the maximum loads supported by each power supply.
It is recommended that the power
supply be mounted vertically & mount
a minimum of 12” above ground
level or deck, 24” below ceiling, and
allow 4” of clearance around power
supply (excluding the mounting side)
to provide for proper air circulation.
Use the provided hardware to mount
properly to wall.
Remove the wiring compartment cover and knockouts
on both ends of the power supply to connect.
Models
A Height
B Width
C Depth
Input
Output
Maximum
wattage
PSDMX-3X96-24
14.00” (15.75”with mounting brackets)
6.62”
4.95”
120-277V AC, 3.3A, 50/60Hz
24 VDC, 3 x 4.0 A,
DMX512
3 x 96 W
12” MIN
use Luminii voltage drop calculator (http://www.luminii.com/voltage-drop-
calculator) to calculate wire gage for low-voltage connection
1
2
24” MIN
A
B
C
power supply
power supply
screw &
anchor
screw driver
120-277VAC wiring
compartment cover
Reference wiring diagrams on page 2. Feed wire
into the terminal block hole. By inserting a small flat
screw driver into the terminal block slot and push down.
Which will open the terminal block hole. Then insert the
wire lead and release the screw driver to secure wire in
place.
120-277VAC wiring
compartment
cover
screw
power supply
24VDC wiring
compartment
cover
terminal block
Question and Answer IconNeed help?

Do you have a question about the luminii PSDMX-3X96-24 and is the answer not in the manual?

luminii PSDMX-3X96-24 Specifications

General IconGeneral
Input Voltage120-277VAC
Output Voltage24VDC
Output Current3 x 4A
DMX Channels3
Weight2.2 lbs
ProtectionOverload, Over Voltage, Short Circuit
Dimensions1.50"
Output Power96W per channel

Summary

Installation and Wiring

Pre-Installation Checks

Verify power supply input voltage, output voltage, and wattage match job requirements.

Mounting and Clearance

Mount vertically 12" above ground, 24" below ceiling, with 4" clearance around unit.

Wiring Compartment Access

Remove wiring compartment cover and knockouts for connection.

Power Connection

Connect power supply wires to terminal blocks following local codes.

Wiring Diagrams

Programming Decoders

Manual Configuration

Steps for selecting mode, setting LED groups, and configuring operation modes.

Standalone and Networked Operation

Configure modes for standalone color, standalone show, or networked DMX operation.

Other Features

Visual Test Run

Perform a visual test run of lighting effects.

Configuration Locking

Lock the current configuration settings to prevent accidental changes.

Factory Reset

Reset the device to its original factory default settings.