3. Surface-Mount Rough-In Panel. Use keyholes with bolts sufficient for
14kg (30lb) load: M6 (1⁄4 in) bolts recommended (mounting hardware
not provided). See Figure 2.
4. Install Power Modules.
a. Install compatible power modules onto DIN rails as shown in Figure3.
Place module1 in position1. If mounting more than one power
module in the rough-in panel, place the next power module directly
next to module1 in position2, followed by position3 and then
position4. Follow the module installation instructions for installing and
wiring. For each 9-DIN wide module after position 1, break out the
respective knock-out, behind the access door in the front cover (see
Figure 4).
Note: When mounting a power supply (QSPS-DH-1-75), it is not
necessary to remove the respective knockout.
b. Install provided end stop to the right of the last module in each row.
c. If a wire landing board (QS-WLB) is needed, it may be placed as
indicated in Figure 3. Wire landing boards are sold separately.
Lutron Electronics Co., Inc.
7200 Suter Road, Coopersburg, PA 18036-1299 USA
Important Notes
Codes: All wiring must be installed in accordance with all local and
national electrical codes.
Cooling: This equipment is air-cooled via natural convection. Mount
in a place where the vented cover will not be blocked. See product
specification for mounting recommendations.
Environment: This equipment is intended for indoor use only. Use in
an ambient of 0°C to 40°C (32°F to 104°F) with a relative humidity
less than 90%, non-condensing.
Mounting Location: Modules (not included) may hum slightly and
the internal relays will click while in use. Mount in a location where
such noise is acceptable.
Mount panel so that line voltage wiring will be at least 1.8m (6 ft)
from audio or electronic equipment and its wiring.
Installation
1. Turn power OFF to all feeds to the panel.
WARNING: Shock Hazard. May result in serious injury or
death. More than one disconnect may be required to
de-energize this device and enclosed modules. Disconnect
all power sources before servicing unit.
2. Remove front cover by removing the bottom cover mounting screws
and loosening the top cover mounting screws.
English
P/N 041555 Rev. B
07/2018
®
)Lutron and Lutron are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. NEC is a registered trademark of the National Fire Protection
Association, Quincy, Massachusetts. ©2015-2018 Lutron Electronics Co., Inc.
Warranty
For warranty information, please see the warranty enclosed with the
product, or visit:
PD4-16-F
www.lutron.com/TechnicalDocumentLibrary/warranty.pdf
PD4-16-F-CE
www.lutron.com/en-US/ResourceLibrary/warranty/Limited%20Comm.pdf
Top Cover
mounting
screws (x2)
Figure 1: Remove front cover
Installation Instructions
Please Read Before Installing
Rough-In DIN Panel
PD4-16-F
120 – 240 V~ 50 / 60 Hz
PD4-16-F-CE
220 – 240 V~ 50 / 60 Hz
Contact Information
www.lutron.com/support
World Headquarters (U.S.A.)
TEL: +1.610.282.3800
Customer Assistance: 1.844.LUTRON1
European Headquarters (United Kingdom)
TEL: +44.(0)20.7702.0657
Customer Assistance: +44.(0)20.7680.4481
FREEPHONE: 0800.282.107
Asian Headquarters (Singapore)
TEL: +65.6220.4666
Customer Assistance: 800.120.4491
Customer Assistance in Other Countries
Mexico: 1.888.235.2910
France: 0800.90.12.18
Germany: 00800.5887.6635
Italy: 800.979.208
Spain: 900.948.944
Northern China: 10.800.712.1536
Southern China: 10.800.120.1536
Hong Kong: 800.901.849
Taiwan: 00.801.137.737
Thailand: 001.800.120.665853
Other areas in Asia: +65.6220.4666
®
Position 3
Position 1
Position 4
Position 2
Figure 3: Install power modules; run power wiring
368 (14.5)
460 (18.1)
409
(16.1)
326
(12.8)
7.9 ( 0.3)
15.8 (0.6)
10.9 (0.4)
–7˚ +7˚
Figure 2: Surface-mount panel (all dimensions: mm [in])
Mount within 7° of vertical.
5. Run power wiring into panel.
WARNING: Shock Hazard. May result in serious injury or
death. More than one disconnect may be required to
de-energize this device. Disconnect all power sources before
servicing unit.
Recommended locations to run power wiring into the panel are shown
in Figure 3.
Run power wiring to power modules. Modules in the panel can be
wired using one or more power feeds. If feeding through Lutron power
modules using line terminals, as shown in image below, total current
must be less than or equal to the maximum current per feed listed in
Table1 to the right. It is recommended that all feed splicing be done
outside of this enclosure.
Model Number Maximum Current Per Feed
LQSE-4A1-D 16 A
LQSE-4S5-230-D 16 A
LQSE-4S8-120-D 16 A
MQSE-xA1-D 16 A
MQSE-xS1-D 16 A
Table 1: Maximum Current Per Feed
Bottom
Cover
mounting
screws (x2)
Knock-outs
Wire landing board
location
Figure 4
6. Install load wiring.
Each DIN power module controls 2 4loads (depending on model
number). Refer to the installation instructions packaged with the DIN
Power Modules.
Label each wire clearly as you wire it to the power module.
NOTE: Refer to module installation sheet for maximum ratings.
Exceeding the maximum ratings can damage the module.
7. Check all wiring before providing power to the panel.
8. Test all load wiring. Turn on input power to the module locations.
Check all connected lighting to ensure it is on. If a circuit breaker trips,
a wiring error exists and must be resolved.
Recommended
low-voltage wiring
entry
Recommended
power wiring
entry
HomeWorks QS
LQSE-4A1-D
lutron.com
COM
MUX
MUX
Zn. 1Prog. Zn. 2Zn. 3Zn. 4
N NNN
DL1 DL2 DL3 DL4
CCI COM
CCI
N
L
120
-
240 V~
50
/
60 Hz 4 A
220
-
240 V~
50
/
60 Hz 4 A
ε
1 A x 4
+1.610.282.3800
Mains
Neutral
HomeWorks® QS
LQSE-4A1-D
lutron.com
COM
MUX
MUX
Zn. 1Prog. Zn. 2Zn. 3Zn. 4
®
N NNN
DL1 DL2 DL3 DL4
CCI COM
CCI
N
L
Inc. Cont. Eq. 243C
120
-
240 V~
50
/
60 Hz 4 A
220
-
240 V~
50
/
60 Hz 4 A
ε
1 A x 4
+1.610.282.3800
Distribution
Panel
120–240 V~
Line/Hot
Figure 5: Power wiring (LQSE-4A1-D shown for reference)
Neutral
To additional modules
Note: If feeding through Lutron
modules using mains terminals,
total current of all modules must
be less than or equal to ratings in
Table 1.
IEC PELV/NEC® Class 2
HomeWorks® QS
LQSE-4A1-D
lutron.com
COM
MUX
MUX
Zn. 1Prog. Zn. 2Zn. 3Zn. 4
®
N NNN
DL1 DL2 DL3 DL4
CCI COM
CCI
N
L
Inc. Cont. Eq. 243C
120
-
240 V~
50
/
60 Hz 4 A
220
-
240 V~
50
/
60 Hz 4 A
ε
1 A x 4
+1.610.282.3800
Earth
Question and Answer IconNeed help?

Do you have a question about the Lutron Electronics PD4-16-F and is the answer not in the manual?

Lutron Electronics PD4-16-F Specifications

General IconGeneral
BrandLutron Electronics
ModelPD4-16-F
CategoryControl Panel
LanguageEnglish