Control/Monitoring
4. Push the PV/SV key, then the SEL key. P-n2 will appear. Set the following:
F. C.
P-n1 2 Direct acting, fails to zero output
P-n2 2 Input type - Type J thermocouple
P-dF 3.0 Input filter constant in seconds
P-SL -40 -40 Lower limit of setpoint range
P-SU 320 160 Upper limit of setpoint range
P-AL 12 High and low zone alarm
P-AH 0
P-dP 0 Number of digits to the right of the decimal point
P-F F. C.
5. Push and hold the Sel key for 3-5 seconds, until P appears. Program as follows:
P 0.0
i 0
d 0.0
AL 32 0 Heater is off below this temp
AH 302 150 Heater is off above this temp
HYS 0.0
6. Push and hold the SEL key for 3-5 seconds. Toggle to dSP1. Set: the following:
dSP1 207
dSP5 135
7. Press the PV/SV key until SV shows. Set SV to 320EF or 160EC.
8. Push and hold the SEL key for 3-5 seconds, until AH appears. Set: LOC to 1, all
parameters locked.