87
CAUTIONS
• Provide an individual power circuit specifically for the air condi-
tioner. As for the method of wiring, refer to the circuit diagram
posted on the inside of the access door.
• Confirm that the cable thickness is as specified in the power source
specification.
• Check the wires and make sure that they are all tightly fastened
after cable connection.
• Be sure to install a ground leakage circuit breaker in wet or moist
areas.
cable specifications
The cord may be different from the list above. It may be used
as the next list. And it can be larger.
0-6A, use 0,75 mm² or 18 AWG. 0-10A, use 1 mm² or 16 AWG.
0-16A, use 1,5 mm² or 14 AWG.
0-20A, use 2,5mm² or 14 AWG. 0-25A, use 2,5 mm² or 12 AWG.
0-32A, use 4 mm²
Power connecting cordPower cord
Type
Normal
cross-section
area Type
Capacity
(BTU/h)
H07RN-F
H05RN-F
0,75~1,5 mm² X3H05VV-F5 000 ~ 13 000
1,5~2,5 mm² X3H05VV-F14 000 ~ 24 000 H07RN-F
1,5 mm² X3
0,75~1,0 mm²X3
Power connecting cord 1
Type
H05RN-F
H05RN-F
0,75 mm² X2
(heat pump)
Main
Power
Supply
1,5~2,5 mm²X3
0,75 mm² X2
(heat pump)
1,5~2,5 mm² X3H05VV-F18 000 ~ 30 000 H07RN-F H05RN-F1,5~2,5 mm²X4
0,75 mm² X2
(heat pump
& optional)
To indoor
2,5 mm² X3H07RN-F18 000 ~ 30 000
H05RN-F
H07RN-F
H05RN-F
0,75 mm² X3
(heat pump)
1,0 mm² X3
1,00 mm² X4
Cooling Only
2,5~4,0 mm² X3H07RN-F24 000 ~ 36 000
H05RN-F
H07RN-F
H05RN-F
0,75 mm² X2
(heat pump
& optional)
0,75 mm²X4
1,0 mm²X4
1,5 mm² X5H07RN-F24 000 ~ 36 000 H05RN-F H05RN-F
0,75 mm² X2
(heat pump)
To outdoor0,75 mm²X4
Normal
cross-section
area
Normal
cross-section
area
To outdoor
To outdoor
To indoor
To indoor