5.0 Dimensions and Fixings
11
© Baxi Heating UK Ltd 2014
DIMENSIONS
A 600mm
B 280mm
C 390mm
D 150mm Ø Min.
E 162.5mm
F 96mm
SIDE FLUE (left and right)
For every 1m of horizontal flue
length, the clearance above the top
of the flue elbow should be 27.5mm
to incorporate the 1.5° fall in the flue
from the terminal to the elbow.
The 1.5° fall provided by the elbow
is to allow condensate to run back to
the boiler, for disposal through the
condensate discharge pipe.
Flue length (Y)
up to 1m
1m - 2m
2m - 3m
Clearance (X)
27.5mm
55mm
82.5mm
360° Orientation
Tube Ø 110mm
D
C
B
A
E
F
Y
At Least 1.5°
X
At Least 1.5°
Fig. 7
Fig. 8