20 Part Number: 000013325 Rev 01 4/16
Installation Section 2
Caution
The refrigeration system warranty will not apply if
the Manitowoc Ice Machine and Manitowoc ICVD
Condensing Unit are not installed according to
specifications. This warranty also will not apply if the
refrigeration system is modified with a condenser,
heat reclaim device, or other parts or assemblies not
manufactured by Manitowoc.
Step 1 Secure the Condenser.
Through-holes are provided to secure the condenser to a
curb, rack or wooden timber.
Warning
The ice machine head section contains refrigerant
charge. The ice machine head section contains
refrigeration valves that must remain closed until proper
installation of the line sets is completed.
Warning
Electrical power to the ice machine head section,
condensing unit or condenser must be disconnected
before proceeding.
Step 2 Route the Refrigeration Tubing.
Route the refrigeration tubing between the ice machine
head section and the condenser or ICVD® condensing unit.
• Maximum lineset exposed on rooftop is 25% of total line
set length.
• A qualified person must perform all roof penetrations.
QuietQube Models Only
• A suction line oil trap is required when rise is more than
6 meters (20 feet).
• Only one trap is allowed in the lineset.
• Shorten the lineset as required, do not coil lineset.
10 METER (30
FEET) MAX.
DISTANCE
30 METER (100 FEET)
MAX. LINESET LENGTH
QUIETQUBE MODELS ONLY: WITH
MORE THAN 6 METER (20 FEET)
RISE, S-TRAP KIT IS REQUIRED
Manitowoc S-Trap Kit
Model
S-Trap Kit
Number
Tubing Size
I0680C IB0686C IB690C
I0686C I0696C I0870C
I0876C IB890C I0976C
I1070C I1076C
K00172
16 mm
(5/8 inch)
IB1090C IB1096C
I1176C I1470C I1476C
I1870C I1876C I2170C
I2176C
K00166
19 mm
(3/4 inch)