Part Number 80-01111-9 7/10 123
Use the following procedure and table to help
determine if a hot gas valve is remaining partially open
during the freeze cycle.
1. Wait five minutes into the freeze cycle.
2. Feel the inlet of the hot gas valve(s).
3. Feel the compressor discharge line.
4. Compare the temperature of the inlet of the hot
gas valves to the temperature of the compressor
discharge line.
Feeling the hot gas valve outlet or across the hot
gas valve itself will not work for this comparison.
The h ot g as val ve o utlet i s on the suction sid e
(cool refrigerant). It may be cool enough to touch
even if the valve is leaking.
The inlet of the hot gas valve and the compressor
discharge line could be h ot e nough to bu rn your
hand. Just touch them momentarily.