40
QUESTIONS TO ASK
POSSIBLE CAUSE
6. Has the knob not moved in 5 days?
After 5 days of no movement the pilot will shut off.
7. Is the ON/OFF switch, located on the valve, in the ON
position?
“O” = OFF; “” = ON
8. Is the ON/MANUAL dial, located on the valve, in the ON
position?
The dial must be fully turned to the ON position.
9. Does it have a Voltage Module? If yes, did the receiver
overheat?
The fireplace goes to pilot if the receiver reaches 140°F.
Troubleshooting the GV60
© 2013, Maxitrol Company