EasyManua.ls Logo

MB 2.6A/AR - Defrosting Operation

Default Icon
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Indoor evaporator high-temperature protection
Condition
T= Indoor exchanger temp.
Compressor Outdoor fan
T<TE8 On On
TE8<T<TE7 On Off
Indoor exchanger temp. up
T>TE7 Off Off
T>TE9 Off Off
Indoor exchanger temp. down
T<TE9 On On
The louver opens to Standard Angle ANGLHEAT when power is on for the first time
8.9 Defrosting operation (Available for heating only).
8.9.1 Defrosting condition: Defrosting starts when either of the following (1)&(2):
(1) A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the
following:
°C
Temp. of evaporator---room temp.
Fan speed is high TH
DEFROST
Fan speed is mid TM
DEFROST
Fan speed is low TL
DEFROST
Breeze Meet only if it is Breeze
(2)Calculate from the end of latest defrost, evaporator high temp. protection only closes
outdoor fan with the compressor still running. Add up to 90 minutes.

Related product manuals