Installation Manual
TypeDUPS20/40 & DR-UPS40 DIN rail peripheral
DUPS20 DC INPUT24-29V 20A BATTERY IN/OUT0~20A
DUPS40 DC INPUT24-29V 40A BATTERY IN/OUT0~40A
DR-UPS40 DC INPUT24-29V 40A BATTERY IN/OUT0~40A
Introduction
DUPS20/40 & DR-UPS40 are DIN rail peripherals for the UPS module.
Like other Mean Wells DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
1Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating.
2The appropriate mounting orientation for the unit is vertical, the TB1 terminals at the bottom. Mounting
orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed.
3Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
10
8
6
Rated Current of
Equipment (Amp)
7A
10A
15A
20A
30A
40A
55A
Cross-section of
Lead(mm
2
)
0.8
1.3
2.1
3.3
5.3
8.4
13.3
Note: 1. Current each wire carries should be de-rated to 80% of the current suggested above when using
5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure
each contact is connected to wires to prevent too much current stress on a single contact.
4Use wires that can withstand temperatures of at least 80°C, such as UL1007.
5Recommended wire strapping length is 5mm (0.197”).
6Recommended screwdriver is 4mm, slotted type.
7The recommended torque setting for terminals is shown as below.
TB1
TB2
DUPS20
4kgf-cm (3.54Lb-in)
5.1kgf-cm (4.42Lb-in)
DUPS40
18kgf-cm (15.6Lb-in)
5.1kgf-cm (4.42Lb-in)
DR-UPS40
18kgf-cm (15.6Lb-in)
5.1kgf-cm (4.42Lb-in)
Question and Answer IconNeed help?

Do you have a question about the Mean Well DUPS20 and is the answer not in the manual?

Summary

Introduction

Installation

Ventilation and Mounting

Ensure proper ventilation clearances (5mm L/R, 40mm top, 20mm bottom) and vertical mounting.

Wiring Guidelines

Use copper wire, refer to AWG chart, ensure secure connections, and use 80°C rated wire.

Torque Specifications

Recommended torque settings for TB1 and TB2 terminals are provided for DUPS20/40 and DR-UPS40.

Mounting Instruction

Warning and Caution

General Safety Warnings

Handle risks of electrical shock, arcs, burns, fire, and short circuits; do not remove the case.

Installation Environment

Install in pollution degree 2, avoid moisture/water, and high ambient temperatures or fire sources.

Operational and Maintenance Safety

Do not exceed rated output; disconnect power before work; use correct fuse rating for fire protection.

Declaration of China RoHS Conformity

Declaration of China VOC Conformity

Declaration of Five PBT TSCA Conformity