Essential safety precautions for handling, installation, and operation of the generator.
Definition of safety symbols indicating risks of damage, injury, or death.
Mandatory earth connection for generator installation and compliance with local regulations.
The final installer is responsible for all necessary safety protections and compliance.
Alternator must be perfectly aligned with the prime mover to avoid dangerous vibrations.
Generators must never run with terminals cover, front covers, or fan guards removed.
Prohibition of using hydro-cleaners or spraying liquids over electrical parts due to IP21 protection.
After long storage or signs of condensation, perform insulation tests by skilled personnel.
Disconnect voltage regulator before testing; dry alternator in oven if results are too low.
Description of underspeed and overload protections, their intervention thresholds, and adjustable settings.
Operations must be carried out by skilled personnel who have read and understood the manual's safety instructions.
During first start-up at reduced speed, check for anomalous noises; stop immediately if detected.
Never use liquids or water; do not use compressed air on internal electrical parts to avoid short-circuits.
High-qualified technicians must perform maintenance and fault search due to inherent dangers.
Take precautions to prevent inadvertent machine restart during maintenance or fault search.
Measured earth resistance must be > 1MΩ; dry windings if lower. Check values with Megger or similar.
Clean externally with compressed air; strictly forbid hydro-cleaners, detergents, or liquids.
Instructions for replacing diode bridges (T30, T18), testing individual diodes with a multimeter.
Troubleshooting steps: check fuse, increase speed, apply temporary battery voltage.
Remedies: reset voltage, check current, cos φ, speed; substitute regulator; check diodes.
Step-by-step procedure to check exciter rotor diodes using battery, lamp, voltmeter.
Step-by-step procedure to calibrate overload protection using Hz and AMP trimmers.
Warranty void if product is stored improperly, modified by unauthorized personnel, used incorrectly, or overloaded.
| Poles | 4 |
|---|---|
| Voltage | 400V |
| Frequency | 50Hz |
| Protection | IP23 |
| Insulation class | H |
| Power Factor | 0.8 |
| Cooling Method | IC01 |
| Phase | Three Phase |