14
selected, the MV value of temperature control output is the change of PID output value.
* 9. #1016 ~ #1023: manually output Settings. Set the duty cycle of the constant output of each channel,
the setting range is: 0 ~ 1000 (unit is 0.1%), the default value is 0.
* 10.# 1149 ~ # 1156: Set the rate of change to limit the increase. # 1157 ~ # 1164: Set the change
rate to limit the decline. Range 0 ~ Range range, when set to 0, it means there is no limit to temperature
rise / cooling, the unit is ℃ / min.
* 11. # 1165 ~ # 1172: Selection of temperature control object characteristics. When the slow heating
object is selected, the temperature control output period, integration time, and derivative time are in
seconds; when the rapid heating object is selected, the temperature control output period, integration
time, and derivative time are in hundred milliseconds;
* 12. #1205 ~ #1212: manual/automatic no disturbance switch Settings. When the manual/automatic
non-disturbance switch setting is effective, the module will switch from manual mode to automatic mode
or from automatic mode to manual mode, and the temperature control output MV value will switch
smoothly to the next output state.
1.5.4 Multi-step function
The Multi-step function Settings of MTC-08-NT buffer (BFM) are shown in table 1-11
Table 1-11 Multi-step function Settings for the buffer (BFM) of MTC-08-NT
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0.0,
denoted by 0.1℃
Default value :0,
time 0 ~
900(minutes)
Default value :0,
time 0 ~
900(minutes)