Instructions
INSTRUCTIONS 730308 Rev. -
Surge-Trap
®
Type 1 SPD for NEMA Type 2 Applications
DANGER
Hazard of Electric Shock, Burn or Explosion
• Thisequipmentmustbeinstalledandservicedonlyby
qualiedelectricalpersonnelinaccordancewithnational
andlocalelectricalcodes.
• Turnoffallpowersupplyingthisequipmentbefore
workingonequipment.
• Alwaysuseaproperlyratedvoltage-sensingdeviceto
conrmpowerisoff.
• Replacealldevices,doorsandcoversbeforerestoring
powertothisequipment.
• Donotapplypetroleum-basedproductsto
non-metallicparts.
Improperinstallationormisapplicationofthesedevices
mayresultinseriousinjurytotheinstallerand/ordamage
toelectricalsystemorrelatedequipment.Protectiveeye
wearandclothingshouldbewornwheneverworking
aroundhazardousvoltages.
Failuretofollowtheseinstructionscouldresultinserious
injuryordeath.
CAUTION
• DonotattempttoopenortampertheSurge-Trap
deviceinanywayasthismaycompromiseperformance
andwillvoidthewarranty.
• Meggerandhi-potentialtestsmaydamagethedevice.
• Disconnectallpowersupplyingtheequipmentand
isolatetheSurge-Trapdevicebeforetesting.
• Priortoinstallation,conrmthattheSurge-Trapisrated
forthecorrectvoltage,currentandfrequencyequivalent
totheapplication.
• ForuseinNEMAType2ApplicationsOnly.
PANEL MOUNT AND WIRING
1. Turnoffallpowersupplyingthisequipment.
2. PanelMount:Removelocknutfromproduct.Punch
outa1/2″enclosureknockoutfromthepanelorthe
mountinglocationascloseaspossibletothewherethe
wireswillterminate.Whereothertypesofmountingare
required,pleaseconsultthefactory.
3. InsertSurge-Trap®SPDwirescarefullythroughthe
knockoutholeandtightenthelocknutto20ft-lb
(2.3Nm)maximumtosecuretheSurge-Trap®SPDto
theenclosure.(AsshowninFigure1)
4. Connectthewiresasshownintheappropriatewiring
diagram.
INSTALLATION
Figure1PanelMount
NUT
USAT9784626662F9784620181info.nby@mersen.com
374MerrimacStreet,Newburyport,MA01950
CANADAT4162529371F4162526572sales.tor@mersen.com
88HornerAvenue,Toronto,Ontario,CanadaM8Z5Y3
ep-us.mersen.com ep-ca.mersen.com
5. OvercurrentProtection:Type1SPDsareULListed
andtestedtobeself-protecting.Theydonotrequire
upstreamprotectionaccordingtoUL1449andSection
285oftheNEC.However,werecommendanupstream
disconnectorbreakerformaintenanceandsafety.
Manyswitchesandcircuitbreakershavelimitations
regardingmorethanonewireinaconnector.Breaker
manufacturerscanprovideinformationonthelimitations
oftheiravailableterminals.Whereadditionalwires
areprohibitedunderthesameterminal,manytimes
installinganewcircuitbreakerisconvenient.Typical
sizesare15,20and30amps.
6. Foroptimaldeviceperformance,useshortestwire
lengthofwireaspossible.Cutofftheexcesswire
insteadofcoilingitup.Avoidsharpbends.
7. Beforeenergizing,installershallverifyserviceand
separatelyderivedsystemNeutraltoGroundbonding
jumperpertheNECrequirements.
Question and Answer IconNeed help?

Do you have a question about the Mersen Surge-Trap and is the answer not in the manual?

Summary

Installation Procedures

Panel Mount and Wiring

Instructions for physically mounting the SPD and connecting wires, including safety steps.

Product Specifications

Product Characteristics Table

Details on SPD models, voltage, phase, frequency, SCCR, and corresponding wiring diagrams.

Wiring Diagrams

System Wiring Configurations

Visual guides illustrating SPD connections for single/split phase and three-phase systems.

Mersen Surge-Trap Specifications

General IconGeneral
CategorySurge Protector
BrandMersen
Product FamilySurge-Trap
Operating Temperature Range-40°C to +85°C
Housing MaterialThermoplastic
StandardsUL 1449, IEC 61643-11