Doc# 100545 • REV C (May 2016) Page 9 of 16
Figure 10: MX2034 wiring with mulple receivers
Connect the eld wiring (16 to 22AWG) in accordance with the appropriate diagrams. For
the MX2034, the minimum power supply voltage is 17 V plus 1 volt for each 50 Ω of loop
resistance. See Graph 1.