4 NormalOperationControl
4.1 ComponentControlduringNormalOperation
Table3‐4.1:Componentcontrolduringnormalcoolingoperation
Component
Wiringdiagram
label
28‐60model Controlfunctionsandstates
Invertercompressor COMP Controlledaccordingtoloadrequirement
DCfanmotor FAN
Fanspeedcontrolledaccordingtoheatexchangertemperature
(T3),outdoorambienttemperature(T4),dischargetemperature
(T5)andcompressorfrequency.
Electronicexpansionvalve EEV
Controlledaccordingtodischargetemperature
Four-wayvalve ST1
Off
Table3‐4.2:Componentcontrolduringheatingoperation
Component
Wiringdiagram
label
28‐60model Controlfunctionsandstates
Invertercompressor COMP Controlledaccordingtoloadrequirement
DCfanmotor FAN
Fanspeedcontrolledaccordingtooutdoorunitheatexchanger
refrigeranttemperature(T3),outdoorambienttemperature(T4)
andcompressorfrequency.
Electronicexpansionvalve EEV
Controlledaccordingtodischargetemperature
Four-wayvalve ST1
On
4.2 CompressorOutputControl
Thecompressorrotationspeediscontrolledaccordingtotheloadrequirement.Beforecompressorstartup,theoutdoor
unitfirstestimatestheindoorunitloadrequirementaccordingtothenominalcapacityofindoorunitscurrentlyrunning,
andthencorrectforambienttemperature.Thecompressorsthenstartupaccordingtothecorrectedloadrequirement.
Duringoperationthecompressorsarecontrolledaccordingtothenominalcapacityofindoorunitscurrentlyrunningand
theindoorunitheatexchangertemperatures.
4.3 CompressorStepControl
Therunningspeedofthecompressorsinrotationspersecond(rps)isonethirdofthefrequency(inHz)oftheelectrical
inputtothecompressormotors.Thecompressorspeedcanbealteredinincrementsof1rps.
4.4 ElectronicExpansionValveControl
ThepositionofelectronicexpansionvalvesEXViscontrolledinstepsfrom0(fullyclosed)to480(fullyopen).
Incoolingmode:
Whentheoutdoorunitisinstandby:
EXVisatposition304(steps)(model28/42)or480(steps)(model36/48/56/60).
Whentheoutdoorunitisrunning:
EXViscontrolledaccordingtodischargetemperature(After3minutesinstandbymode).
Inheatingmode:
Whentheoutdoorunitisinstandby:
EXVisatposition304(steps)(model28/42)or480(steps)(model36/48/56/60).
Whentheoutdoorunitisrunning:
EXViscontrolledaccordingtodischargetemperature(After3minutesinstandbymode).
