e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from 
    various parts of the system.     
f) Make sure that cylinder is situated on the scales before recovery takes place.    
g) Start the recovery machine and operate in accordance with manufacturer's instructions.    
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i)  Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)  When the cylinders have been filled correctly and the process completed, make sure that 
    the cylinders and the equipment are removed from site promptly and all isolation valves 
    on the equipment are closed off.     
k) Recovered refrigerant shall not be charged into another refrigeration  system unless it has 
    been cleaned and checked.
14.Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of 
refrigerant. The label shall be dated and signed. Ensure that there are labels on the 
equipment stating the equipment contains flammable refrigerant.
15.Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is 
recommended good practice that all refrigerants are removed safely. When transferring 
refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are 
employed. Ensure that the correct number of cylinders for holding the total system charge is 
available. All cylinders to be used are designated for the recovered refrigerant and labelled 
for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be 
complete with pressure relief valve and associated shut-off valves in good working order. 
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. 
The recovery equipment shall be in good working order with a set of instructions concerning 
the equipment that is at hand and shall be suitable for the recovery of the flammable 
refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated 
weighing scales shall be available and in good working order. Hoses shall be complete with 
leak-free disconnect couplings and in good condition.
The recovered refrigerant shall be processed according to local legislation in the correct 
recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in 
recovery units and especially not in cylinders. If compressors or compressor oils are to be 
removed, ensure that they have been evacuated to an acceptable level to make certain that 
flammable refrigerant does not remain within the lubricant. The compressor body shall not 
be heated by an open flame or other ignition sources to accelerate this process. When oil is 
drained from a system, it shall be carried out safely.