1. If the compressor frequency keeps lower than RECOILINFRE for Te minutes, the AC will rise the
frequency to RECOILFRE for Tf seconds and then resume to former frequency. For M4OC-36HRDN1-Q,
RECOILINFRE=45Hz, RECOILFRE=48Hz,Te=120,Tf=180; For M5OA-36HRDN1-Q, RECOILINFRE=45Hz,
RECOILFRE=48Hz, Te=90,Tf=100; For other models, RECOILINFRE=50Hz, RECOILFRE=62Hz,
Te=120,Tf=180.
2. During the Tf seconds, the EXV and indoor units keep the current running mode(except
M5OA-36HRDN1-Q model), the frequency will not be limited by the compressor discharge temp. and the
current. For M5OA-36HRDN1-Q model, the EXV will keep 300p while the indoor units will keep the current
running mode.
3. If the outdoor ambient is higher than 15 during the oil return, the AC quit oil return.
7.5.9 Compressor preheating functions
----Preheating permitting condition:
If T4(outdoor ambient temperature)3 and the machine connects to powe r supply no longer than 5
seconds or if T43 and compressor has stopped for over 3 hours, the compressor heating cable will
work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
----Preheating release condition:
If T45 or the compressor starts running, preheating function will stop.
7.5.10 Compressor crankcase heater
When T4<3 and the compressor is not running, the crankcase heater will be active.
When T45 or the compressor starts up, the crankcase heater will stop work.(For M5OA-36HRDN1-Q,T4
8)