EasyManuals Logo

Midea MCD-18CRN1-Q User Manual

Midea MCD-18CRN1-Q
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #254 background imageLoading...
Page #254 background image
Troubleshooting
250 Electrical Control
f. High temperature protection of condenser
High temperature protection of condenser
Check the resistance of the temp. sensor
according to Appendix 1, is it normal?
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is
defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
Replace the sensor
No
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MCD-18CRN1-Q and is the answer not in the manual?

Midea MCD-18CRN1-Q Specifications

General IconGeneral
BrandMidea
ModelMCD-18CRN1-Q
CategoryAir Conditioner
LanguageEnglish

Related product manuals