Page 12 
Troubleshooting
Problem Possible Causes
Dust is emitted from 
either the indoor or 
outdoor unit  
The unit may accumulate dust during extended periods of non-use, which 
will be emitted when the unit is turned on. This can be mitigated by covering 
the unit during long periods of inactivity.  
The unit emits a 
bad odor  
The unit may absorb odors from the environment (such as furniture, cooking, 
cigarettes, etc.) which will be emitted during operations. 
The unit’s filters have become moldy and should be cleaned.
The fan of the 
outdoor unit 
does not operate  
During operation, the fan speed is controlled to optimize product operation.
Troubleshooting Tips
When troubles occur, please check the following points before contacting a repair company. 
Problem Possible Causes Solution
The unit 
is not 
working 
Power failure Wait for the power to be restored
The power switch is o Turn on the power
The fuse is burned out Replace the fuse
Remote control batteries are dead Replace the remote control batteries
The unit’s 3-minute protection has 
been activated 
Wait three minutes after restarting the unit 
Poor cooling 
performance 
Temperature setting may be higher 
than the ambient room temperature 
Lower the temperature setting
The heat exchanger on the indoor 
or outdoor unit is dirty 
Clean the aected heat exchanger
The air filter is dirty
Remove the filter and clean it according 
to instructions
The air inlet or outlet of either unit 
is blocked
Turn the unit o, remove the obstruction 
and turn it back on 
Doors and windows are open
Make sure that all doors and windows are 
closed while operating the unit 
Excessive heat is generated by 
sunlight
Close windows and curtains during 
periods of high heat or bright sunshine 
Low refrigerant due to leak or 
long-term use
Check for leaks, re-seal if necessary and 
top o refrigerant 
The unit 
starts and 
stops 
frequently 
There’s too much or too little 
refrigerant in the system  
Check for leaks and recharge the system 
with refrigerant  
There is air, incompressible gas or 
foreign material in the refrigeration 
system.  
Evacuate and recharge the system with 
refrigerant
System circuit is blocked
Determine which circuit is blocked and replace 
the malfunctioning piece of equipment 
The compressor is broken Replace the compressor
The voltage is too high or too low Install a manostat to regulate the voltage
Poor heating 
performance 
The outdoor temperature is lower 
than 7°C (44.5°F) 
Check for leaks and recharge the system 
with refrigerant 
Cold air is entering through doors 
and windows
Make sure that all doors and windows are 
closed during use  
Low refrigerant due to leak or 
long-term use
Check for leaks, re-seal if necessary and 
top o refrigerant