36
★ 2 times
X E1
Communication malfunction between indoor and
outdoor units
E2
★ 4 times
X E3 Indoor fan speed malfunction
★ 5 times
X E4 Indoor room temperature sensor (T1 ) malfunction
★ 6 times
X E5
Evaporator coil temperature sensor (T2)
malfunction
★ 8 times
X EE Water-level alarm malfunction
★ 1 times
F0 Current overload protection
★ 2 times
F1
Outdoor ambient temperature sensor (T4 )
malfunction
E4
★ 3 times
F2
Condenser coil temperature sensor (T3)
malfunction
E4
★ 4 times
F3
Compressor discharge temperature sensor (T5)
malfunction
E4
★ 5 times
F4 Outdoor unit EEPROM parameter error
E0
★ 6 times
F5 Outdoor fan speed malfunction
E8
★ 7 times
F6
Indoor coil outlet pipe sensor(Located on outdoor
unit low pressure valve)
——
★ 8 times
F7
Communication malfunction between Cassette
optional lift panel and the unit.
——
★ 9 times
F8 Cassette optional lift panel malfunction
——
F9 Cassette optional lift panel not closed
——
★ 1 times ★
P0 Inverter module (IPM) malfunction
P6
★ 2 times ★
P1 Over-voltage or under-voltage protection
E5
★4 times ★
P3 Low ambient temperature cut off in heating
★ 5 times ★
P4 Compressor drive malfunction
★ 6 times ★
——
Indoor units mode conflict
★ flash , light, X extinguished
Outdoor unit error display
MCH2U-18PHH2, MCH3U-27PHH2, MCH4U-36PHH2, MCH5U-48PHH2;
Display
Error
E0 Outdoor unit EEPROM parameter error
F4
E2 Communication malfunction between indoor and outdoor units
E1
E3
Communication malfunction between IPM board and outdoor main
control board
E4
Outdoor temperature sensor (coil sensor T3,ambient sensor T4,
Compressor discharge sensor T5、indoor coil outlet pipe sensor T2B)
malfunction
F2/F1/F3/F6