16
----If the temperature increase and T5≧110℃
(230 ℉), decrease the frequency to a lower
level every 2 minutes till to F1.
---If T5≧115℃ (239 ℉) for 10 seconds, the
compressor stops and then restart untill
T5<90℃ (194 ℉).
6.3.3 Fan Speed Malfunction
---- If outdoor fan speed is lower than
100RPM or higher than 2400RPM for 60
seconds or more, the unit stops and LED
displays
E8
failure code.
6.3.4 Inverter Module Protection.
---- The inverter protection module ensures
that faults related to current, voltage, or
temperature does not damage the inverter.
If these protections are triggered, the A/C
unit stops and the LED displays the failure
code.
The unit restarts 3 minutes after the
protection mechanism has turned off.
6.3.5 Low Voltage Protection
V O L T A G E
N o lim it
V O L T_ LT M _ F R E Q 1_ A D D
V O LT _ LT M _F R EQ 2 _ AD D
Note: If low voltage protection triggers and
voltage is not restored to normal within 3
minutes, the protection remains active
even after a machine restart.
6.3.6 Compressor Current Limit
Protection
The temperature interval for the current limit
is the same as the range of the T4
frequency limit.
Cooling mode:
CoolReturnI The difference between
current limit
and shutdown current
CoolT4Zone5I