16
Outside diameter
Torque
Additional
tightening
torque
mm
inch
N.cm
N.cm
Ф12.7
1/2
4950
6030
Ф19
3/4
9720
11860
5.3.3 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be
leak tested and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or
outdoor unit connections by a soft brush to check for leakage of the connecting points of
the piping. If bubbles come out, the pipes have leakage.