EasyManuals Logo

Midea MFE-60ARN1-RB4W User Manual

Midea MFE-60ARN1-RB4W
57 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
16
Outside diameter
Torque
Additional
tightening
torque
mm
inch
N.cm
N.cm
Ф12.7
1/2
4950
6030
Ф19
3/4
9720
11860
5.3.3 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be
leak tested and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or
outdoor unit connections by a soft brush to check for leakage of the connecting points of
the piping. If bubbles come out, the pipes have leakage.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MFE-60ARN1-RB4W and is the answer not in the manual?

Midea MFE-60ARN1-RB4W Specifications

General IconGeneral
BrandMidea
ModelMFE-60ARN1-RB4W
CategoryAir Conditioner
LanguageEnglish

Related product manuals