38
When the evaporator coil temp.T2 keeps lower than T2CoolIn for 30 minutes, the
compressor and outdoor fan will shut off. When T2 is higher than T2CoolExit, the
compressor and outdoor fan will restart up.
Condition 2:
T2CoolExit
T2
On
Off
T2CoolIn-2
When the evaporator coil temp.T2 keeps lower than T2CoolIn-2 for 20 minutes, the
compressor and outdoor fan will shut off. When T2 is higher than T2CoolExit, the
compressor and outdoor fan will restart up.
Condition 3:
T2CoolExit
T2
On
Off
T2CoolIn-4
When the evaporator coil temp.T2 keeps lower than T2CoolIn-4 for 8 minutes, the
compressor and outdoor fan will shut off. When T2 is higher than T2CoolExit, the
compressor and outdoor fan will restart up.
The others modes:
When T2-1 and lasts for 4 minutes, the indoor has no capacity demand and resume
till T210.
8.3.3.4 Condenser high temperature T3 protection
When T3T3CoolStop_ADD for 3 seconds, the compressor will shut off. When T3
T3CoolRts_ADD,the compressor will restart.
Model
T3CoolStop_ADD
T3CoolRts_ADD
MFE-60AMN1-RB4W
65
60
MFE-60ARN1-RB4W
(2T0043800026)
65
60
MFE-60ARN1-RB4W
65
48