10.1.3.3 The restart of the compressor shall execute the delay protection.
10.1.4 Condenser high temperature protection
10.1.4.1 Only available to cooling and dehumidifying mode.
10.1.4.2 Action condition
10.1.4.3 Delay protection should be performed when the compressor restarts.
10.1.5 Outdoor protection
When outdoor protection signal is high level(last 4 seconds), outdoor unit will perform
protection: the whole machine will be shut down while the indoor unit will indicate the
corresponding protection signal(Ed).
The A/C will recover if outdoor errors are eliminated after the outdoor protection occurs.
Condition Outdoor fan Compressor
T22°Clast 3 minutes
Off Off
T27°C
On On
Condition Outdoor fan Compressor
Condenser temp.65°Clast 3 seconds
Off Off
Condenser temp.<52°C On On