DM16-01.01.25en    Floor Standing MFM 
37    Service manual 
T1-TS
On
Off
 
 
9.3.1.3 Indoor fan running rules: 
When  the  compressor  is  on,  the  indoor  fan  can  be  set  to  high/low/auto.  And  the  anti-cold  wind 
function has the priority. 
Autofanaction:
T1-Ts
Low
High
 
9.3.1.4 Defrost (only available to heating mode) 
---Defrosting Conditions 
  Starting Of Defrosting Condition (meet one of the following is ok): 
(1)Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to 
40 minutes, then consecutive 3 minutes less than -5 degrees (Just for the    AC  is  turn  on  , 
whether or not the heating mode the temperature was detected, start to statistical time when reach 
the temperature condition . Shut down or defrosting calculate time again). 
(2) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to 
60 minutes, then consecutive 3 minutes less than -4 degrees (Just for the    AC  is  turn  on  , 
whether or not the heating mode the temperature was detected, start to statistical time when reach 
the temperature condition . Shut down or defrosting calculate time again). 
(3) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to 
80 minutes, then consecutive 3 minutes less than -2 degrees (Just for the    AC  is  turn  on  , 
whether or not the heating mode the temperature was detected, start to statistical time when reach 
the temperature condition . Shut down or defrosting calculate time again). 
(4) Under evaporator high temperature protection, the accumulated time when outdoor fan motor is 
off and compressor is on reaches up to over 90 minutes .( Shut down or defrosting or T3 is over 
15°C, calculate time again.) 
 
--- Defrosting Action 
Four-way valve, indoor fan, outdoor fan are shut down. Compressor keeps on.