Floor Standing MFM    DM16-01.01.25en 
Service manual    48 
10.2.5 High temperature protection ofcondenser 
 
 
 
10.2.6 High pressure protection 
 
 
High temperature protection of condenser 
Check the resistance of the temp. sensor 
according to Appendix 1, is it normal? 
Possible reason 
1.  Air or other gas in the refrigerant. 
2.  Heat exchanger is dirty 
3.  Outdoor fan or fan blade is defective
4.  Outdoor unit is bad ventilation 
5.  Refrigerant is leakage 
6.  Outdoor PCB is defective 
Replace the sensor 
No   
Yes