MCAC-ATSM-2014-01 R410A Mini Split Chiller 50Hz
27
f1 capacity correction factor
fk1 compressor power input correction factor
fx1 total power input correction factor
13.3 Minimum water volume
If the total water volume in the system is less than the value in the table above, the additional water tank is
necessary in order to avoid the compressor On/Off frequency.
The minimum size of the water tank is calculated as:
Size of additional water tank(L)=Minimum water volume (L) –Actual water volume(L).