MCAC-ATSM-2014-01 R410A Mini Split Chiller 50Hz
41
E3: Inlet water temperature sensor checking channel is abnormal
E4: Outdoor ambient temperature sensor checking channel is abnormal
Check whether the wiring of inlet water temperature
sensor is broken.
Check whether the inlet water temperature sensor is
broken: see whether the resistance of inlet water
temperature sensor is wrong.
Replace the inlet water temperature sensor.
Check whether the wiring of outdoor ambient
temperature sensor is broken.
Check whether the outdoor ambient temperature
sensor is broken: see whether the resistance of
outdoor ambient temperature sensor is wrong.
Replace the outdoor ambient temperature
sensor.