R410A Mini Split Chiller 50Hz MCAC-ATSM-2014-01
46
P1: High pressure protection
High pressure protection.
Whether the wiring between the high pressure switch
and main control board is connected well and
correctly.
Whether the high pressure switch is broken.
Validate: Short connect the high pressure switch
socket, check whether the system can run normally.
Replace outdoor main board.
Check whether the outdoor ambient temperature is
too high.
Check whether the outdoor unit is bad ventilation.
Make the outdoor unit ventilate well.
Check whether the heat exchanger is dirty.
Clean the heat exchanger.
Check whether the refrigerant pipe is blocked.
Drop refrigerant, then use the high pressure
nitrogen or refrigerant to blow pipe,
vacuumize and add the refrigerant again.
Replace high pressure switch.
Whether the discharge temperature controller gets
faulty.
Replace discharge temperature controller.
Check whether the refrigerant system is ok.