Midea DC Fan Coil Unit
6
Power supply
V/Ph/Hz
220-240/1/50
Air flow (H/M/L)
m
3
/h
1525/1212/1088
1785/1545/1397
1857/1410/1191
CFM
897/712/640
1050/908/821
1092/829/700
Cooling
1
Capacity (H/M/L)
kW
5.82/5.07/4.75
8.75/7.97/7.4
8.76/7.29/6.45
Water flow rate(H/M/L)
m
3
/h
1.04/0.9/0.83
1.57/1.43/1.31
1.58/1.30/1.15
Water pressure drop(H/M/L)
kPa
16.4/12.6/10.9
33.9/30/24
33/22.6/17.7
Power input(H/M/L)
W
77/42/32
107/71/54
125/58/38
Heating
2
Capacity (H/M/L)
kW
8.52/6.36/5.93
11.7/9.88/9.27
12.29/9.17/8.24
Water flow rate(H/M/L)
m
3
/h
0.68/0.59/0.55
0.96/0.89/0.84
0.99/0.83/0.76
Water pressure drop(H/M/L)
kPa
34/26.6/23.5
42.4/36.6/32.6
48.7/32.5/27
Power input(H/M/L)
W
76/42/32
107/72/55
126/58/38
Heating
3
Capacity (H/M/L)
kW
8.37/7.24/6.76
12.19/11.21/10.52
12.47/10.53/9.53
Water flow rate(H/M/L)
m
3
/h
0.78/0.67/0.63
1.10/1.00/0.95
1.14/0.96/0.87
Water pressure drop(H/M/L)
kPa
43.8/33.5/29.3
52.1/44.9/40.6
62.1/45.7/38.3
Power input(H/M/L)
W
76/41/32
107/72/55
126/58/38
Sound pressure level
(H/M/L)
dB(A)
46/41/38
48/44/42
49/43/38
Rated current
A
0.6
0.9
1
Fan motor
Type
DC motor
DC motor
DC motor
Quantity
1
1
1
Fan
Type
Centrifugal, forward-curved Blades
Quantity
1
1
1
Coil
Row
2
3
3
Max. Working pressure
MPa
1.6
Coil length x height
mm
1990x252
2050x252
2080x252
Fin type
Hydrophilic aluminum
Number of circuits
Cold water 9;
Cold water 14; Hot water 4
Hot water 3
Fin spacing
mm
1.5
Diameter
mm
Φ7
Panel
Dimensions W×D
mm
950×45×950
Packing W×D
mm
1035×90×1035
Net weight
kg
6
Gross weight
kg
9
Body
Dimensions
mm
840×300×840
Packing
mm
900×330×900
Net weight
kg
27.5
30
30
Gross weight
kg
32.4
35
35
Pipe connection
Water inlet/outlet pipe
inch
Cold water: RC3/4; Hot water: RC1/2
Drain pipe
mm
ODΦ32
Note:
Based on Eurovent conditions:
H: High fan speed; M: Medium fan speed; L: Low fan speed.
1Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature 7°C /12°C,
high fan speed.
2Heating mode1: (4-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 65/55°C,
high fan speed.
3Heating mode2 (4-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 70/60°C,
high fan speed.