MCAC-KTSM-2007-2 Capacity Tables
Four Way Cassette Type 15
6. Capacity Tables
Cooling Capacity Table
Unit: W
Model
Water
inlet
temp.
(ā„ƒ)
Water
FV
(LPM)
Water
PD
(kPa)
Air inlet condition
DB24ā„ƒ
DB25ā„ƒ
DB26ā„ƒ
DB27ā„ƒ
DB28ā„ƒ
WB17ā„ƒ
WB18ā„ƒ
WB19ā„ƒ
WB19.5ā„ƒ
WB21ā„ƒ
SH
TH
SH
TH
SH
TH
SH
TH
SH
TH
MKA-600
5
10
13.5
3439
4047
3537
4449
3636
4860
3823
5074
3823
5717
15
30.4
3716
4735
3850
5217
3975
5708
4172
5958
4207
6736
20
54
3913
5181
4056
5708
4199
6262
4404
6539
4467
7406
25
84.4
4029
5458
4181
6012
4333
6593
4547
6896
4627
7817
6
10
13.5
3296
3734
3404
4127
3502
4538
3689
4744
3689
5387
15
30.4
3555
4368
3689
4842
3815
5333
4011
5583
4047
6352
20
54
3734
4788
3877
6218
4020
5851
4225
6137
4297
6995
25
84.4
3841
5038
3993
5601
4154
6173
4359
6477
4449
7388
7
10
13.5
3162
3413
3270
3806
3368
4208
3555
4413
3564
5047
15
30.4
3395
4002
3529
4467
3654
4958
3850
5100
3895
5967
20
54
3555
4386
3707
4904
3850
5449
4056
5726
4118
6575
25
84.4
3654
4618
3815
5172
3966
5753
4181
6039
4261
6959
8
10
13.5
3028
3082
3136
3475
3234
3877
3421
4083
3430
4717
15
30.4
3243
3627
3368
4091
3502
4574
3698
4815
3743
5574
20
54
3386
3975
3529
4493
3672
5029
3877
5306
3949
6155
25
84.4
3466
4199
3627
4744
3788
5315
3993
5610
4083
6512
9
10
13.5
2894
2894
3002
3145
3109
3547
3296
3743
3305
4368
15
30.4
3082
3243
3216
3707
3341
4181
3538
4431
3591
5181
20
54
3207
3564
3359
4083
3502
4610
3707
4878
3779
5726
25
84.4
3287
3761
3448
4306
3600
4878
3815
5163
3904
6066
10
10
13.5
2760
2760
2877
2877
2975
3207
3162
3404
3180
4029
15
30.4
2930
2930
3064
3314
3189
3788
3386
4029
3439
4779
20
54
3037
3145
3189
3654
3332
4181
3538
4449
3618
5288
25
84.4
3109
3323
3270
3859
3421
4422
3636
4708
3725
5601
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)