EasyManua.ls Logo

Midea MKB-300 - Page 21

Midea MKB-300
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MCAC-KTSM-2007-2 Capacity Tables
Four Way Cassette Type 19
Cooling Capacity Table
Unit: W
Model
Water
inlet
temp.
()
Water
FV
(LPM)
Water
PD
(kPa)
Air inlet condition
DB24
DB25
DB26
DB27
DB28
WB17
WB18
WB19
WB19.5
WB21
SH
TH
SH
TH
SH
TH
SH
TH
SH
TH
MKA-1200
5
25
18.2
6858
8651
7094
9517
7322
10418
7680
10873
7750
12282
32
29.8
7059
9141
7313
10060
7558
11022
7925
11503
8022
13017
35
35.6
7226
9526
7488
10497
7750
11494
8127
12011
8249
13603
40
46.5
7392
9832
7637
10838
7908
11879
8293
12413
8424
14066
6
25
18.2
6569
7978
6797
8844
7033
9736
7392
10191
7462
11591
32
29.8
6753
8433
7007
9360
7252
10305
7619
10786
7715
12290
35
35.6
6902
8800
7164
9762
7427
10751
7803
11267
7925
12842
40
46.5
7024
9089
7304
10086
7575
11118
7960
11652
8100
13734
7
25
18.2
6272
7304
6508
8162
6736
9045
7103
9054
7173
10882
32
29.8
6438
7724
6701
8634
6946
9579
7313
9849
7418
11547
35
35.6
6578
8057
6849
9010
7112
9999
7488
10506
7610
12081
40
46.5
6683
8328
6972
9316
7243
10348
7628
10873
7768
12509
8
25
18.2
5983
6613
6220
7471
6456
8345
6814
8791
6893
10174
32
29.8
6132
7007
6395
7908
6639
8844
7016
9316
7121
10795
35
35.6
6255
7304
6526
8258
6788
9238
7173
9745
7296
11293
40
46.5
6360
7558
6639
8538
6919
9561
7304
10086
7444
11704
9
25
18.2
5695
5922
5940
6762
6167
7637
6535
8074
6613
9447
32
29.8
5835
6272
6088
7173
6342
8100
6718
8573
6823
10034
35
35.6
5940
6543
6211
7488
6482
8468
6858
8966
6989
10506
40
46.5
6027
6771
6316
7750
6587
8765
6981
9281
7121
10891
10
25
18.2
5415
5415
5660
6053
5887
6919
6255
7357
6342
8713
32
29.8
5529
5529
5791
6421
6045
7339
6421
7812
6526
9264
35
35.6
5625
5773
5896
6709
6167
7672
6552
8170
6683
9701
40
46.5
5703
5975
5992
6946
6272
7952
6657
8468
6806
10060
Remark
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)