Capacity Tables MCAC-KTSM-2007-2
32 Compact Four Way Cassette Type
Cooling Capacity Table
Unit: W
Model
Water
inlet
temp.
()
Water
FV
(LPM)
Water
PD
(kPa)
Air inlet condition
DB24
DB25
DB26
DB27
DB28
WB17
WB18
WB19
WB19.5
WB21
SH
TH
SH
TH
SH
TH
SH
TH
SH
TH
MKB-400
5
6
4.6
1852
2188
1911
2407
1961
2626
2062
2744
2062
3089
8
8.1
1970
2466
2037
2710
2096
2963
2205
3097
2222
3493
10
12.7
2045
2651
2121
2921
2197
3198
2298
3342
2331
3779
12
18.2
2121
2811
2197
3097
2273
3400
2382
3552
2424
4023
6
6
4.6
1784
2020
1835
2230
1894
2449
1995
2567
1995
2912
8
8.1
1885
2273
1953
2517
2012
2769
2121
2895
2138
3299
10
12.7
1843
1961
2028
2719
2104
2996
2214
3131
2239
3569
12
18.2
2020
2601
2104
2887
2180
3182
2289
3333
2331
3804
7
6
4.6
1709
1843
1768
2054
1818
2273
1919
2390
1919
2727
8
8.1
1801
2079
1869
2323
1936
2576
2037
2702
2054
3097
10
12.7
1869
2239
1944
2508
2012
2778
2121
3190
2155
3358
12
18.2
1927
2382
2003
2828
2087
3156
2197
3409
2230
3577
8
6
4.6
1633
1667
1692
1877
1751
2096
1852
2205
1852
2550
8
8.1
1717
1885
1784
2121
1852
2374
1953
2500
1978
2895
10
12.7
1776
2028
1852
2298
1927
2567
2037
2710
2062
3139
12
18.2
1826
2163
1911
2441
1986
2735
2104
2879
2138
3342
9
6
4.6
1566
1566
1624
1700
1675
1919
1776
2028
1784
2365
8
8.1
1641
1683
1709
1927
1776
2172
1877
2298
1894
2685
10
12.7
1692
1818
1860
2079
1835
2348
1944
2491
1978
2912
12
18.2
1734
1936
1818
2214
1894
2508
2012
2651
2045
3114
10
6
4.6
1431
1490
1549
1549
1608
1734
1709
1843
1717
2180
8
8.1
1557
1557
1624
1717
1692
1970
1801
2087
1818
2475
10
12.7
1599
1599
1675
1860
1751
2129
1860
2264
1894
2693
12
18.2
1641
1709
1725
1986
1801
2273
1919
2416
1961
2870
Remark
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)