AC Fan Coil Unit Two-pipe Wall-
- 10 - 
MKG-500-D / MKG-600-D   
Model    MKG-500-D  MKG-600-D 
Power supply  V/Ph/Hz
220-240/1/50 
Air flow (H/M/L) 
m3/h  841/723/594  915/836/714 
CFM  495/425/349  538/492/420 
Cooling 
Capacity (H/M/L)  kW  4.01/3.61/3.1  4.61/4.33/3.84 
Water flow rate(H/M/L)  m3/h  0.72/0.65/0.56  0.83/0.78/0.69 
Water pressure drop(H/M/L)  kPa  47.1/33.5/29.7  51/39.5/34 
Heating 
Capacity (H/M/L)  kW  4.39/3.8/3.27  4.55/4.2/3.82 
Water flow rate(H/M/L)  m3/h  0.8/0.69/0.6  0.83/0.76/0.69 
Water pressure drop(H/M/L)  kPa  48.6/40.8/31.7  48/43/33 
Power input (H/M/L)  W  60/54/48  72/60/55 
Current Input  A  0.22  0.29 
Sound pressure level  dB(A)  39/33/28  40/34/29 
Fan motor 
Type  Low noise 3-speed fan motor  Low noise 3-speed fan motor 
Quantity  1  1 
Fan 
Type  Tangential fan  Tangential fan 
Quantity  1  1 
Coil 
Row  2  2 
Diameter  mm  Φ7  Φ7 
Tube pitch(a)xrow pitch(b)  mm  21×13.37  21×13.37 
Dimension (W×H×D)  mm  785×315×26.74  785×315×26.74 
Fin spacing  mm  1.5  1.5 
Fin type  Hydrophilic aluminium  Hydrophilic aluminium 
Circuit  5  5 
Max. working pressure  MPa  1.6  1.6 
Body 
Net dimensions (W×H×D)  mm  1072×315×232  1072×315×232 
Packing size (W×H×D)  mm  1180×415×315  1180×415×315 
Net weight  kg  15.8  15.8 
Gross weight  kg  19.4  19.4 
Pipe connections 
Water inlet/outlet pipe  inch  G3/4  G3/4 
Drain pipe  mm  ODΦ20  ODΦ20 
Notes: 
1. H: high fan speed; M: medium fan speed; L: low fan speed 
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°C WB. 
Heating Conditions: Entering Water 50°C, Enter air temperature 20°C, and water flow is same to the cooling conditions. 
3. Noise is tested in semi-anechoic test room.