AC Fan Coil Unit Two-pipe Wall-mounted Series
 
- 5 - 
6. Specifications 
6.1 S type panel 
MKG-250-B / MKG-300-B / MKG-400-B   
Model  MKG-250-B  MKG-300-B  MKG-400-B 
Power supply  V/Ph/Hz  220-240/1/50 
Air flow (H/M/L) 
m3/h  425/390/350  510/470/390  680/550/460 
CFM  250/230/205  300/275/230  400/325/270 
Cooling 
Capacity (H/M/L)  kW  2.63/2.41/2.16  2.97/2.47/2.12  3.28/2.83/2.41 
Water flow rate  L/h  452    511    564   
Water pressure drop  kPa  29.4  35.6  43.5 
Heating 
Capacity (H/M/L)  kW  3.36/3.1/2.79  3.91/3.26/2.77  4.37/3.73/3.17 
Water pressure drop  kPa  27.3  32.9  40.8 
Power input  W  24  37  40 
Current input  H  A  0.12  0.18 
Sound pressure level  dB(A)  30/24/20  35/29/24  37/31/26 
Fan motor 
Type  Low noise 4-speed fan motor 
Quantity  1 
Fan 
Type  Tangenti al fan 
Quantity  1 
Coil 
Row  2 
Diameter  mm  Φ7 
Tube pitch(a)  ×  row pitch(b)  mm  21×13.37 
Dimension (W×H×D)  mm  635×315×26.74 
Fin spacing  mm  1.5 
Fin type  Hydrophilic aluminum 
Circuit  5 
Max. working pressure  MPa  1.6 
Body 
Net dimensions (W×H×D)  mm  915×290×230 
Packing size (W×H×D)  mm  1020×390×315 
Net weight  kg  13  13  13.3 
Gross weight  kg  16.3  16.3  16.7 
Pipe 
connections 
Water inlet/outlet pipe  inch  G3/4 
Drain pipe  mm  ODΦ20 
Notes: 
1. H: high fan speed; M: medium fan speed; L: low fan speed 
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°C WB. 
Heating Conditions: Entering Water 50°C, Enter air temperature 20°C, and water flow is same to the cooling conditions. 
3. Noise is tested in semi-anechoic test room.