AC Fan Coil Unit Two-pipe Wall-mounted Series
 
- 15 - 
Main PCB port description: 
No.  Bit No.  Description  Remarks 
1  CN10  POWER: Mains input  Standard 
2  CN29  CAN: Cooling and heating 2-way/3-way valve null line  Standard 
3  CN14  ACN: Cooling and heating 2-way/3-way valve null line
Reserved 
4  CN11 
PUMP: Water pump output port    Reserved (the 
whole machine 
cannot be realized)
5  CN6  VALVE-H: Heating 2-way/3-way valve live line  Customized 
6  CN7  VALVE-C: Cooling 2-way/3-way valve live line  Standard 
7  CN16 
N: Null line output port for AC fan 
Standard 
L: Low fan speed output port for AC fan 
M: Medium fan speed output port for AC fan 
H: High fan speed output port for AC fan 
HH: Super-high wind profile reserved port for AC fan 
8  CN2  SWING: Swing motor port  Standard 
9  CN31  T2C: Refrigerating pipe temperature sensor port  Standard 
10  CN3  ON/OFF: Remote on/off port  Standard 
11  CN32  T1: Room temperature sensor port  Standard 
12  CN8  T2H: Heating pipe temperature sensor port  Customized 
13  CN18  WATER: Water level switch port 
Reserved (the 
whole machine 
cannot be realized)
14  CN15  DISPLAY:Display panel docking port (nine pin)  Standard 
15  CN21  Dial code small board docking port  Standard 
16  CN20  E - side program burning port  Standard 
17  CN9  DEBUG: Main control program burn port  Standard 
18  CN22  PQE: Modbus communication port 
19  CN23  XYE: Centralized control communication port  Standard 
20  CN27 
TRANS OUT:0-10V value 
powered linear transformer 
secondary 
Customized 
21  CN25  0-10V valve control signal output  Customized 
22  CN12  ALARM: Fault alarm output  Customized 
23  CN19  Electrically heated N-wire control port 1  Customized 
24  CN26  Electrically heated N-wire control port 2  Customized 
25  CN13  Electrically heated L-wire control port 1  Customized 
26  CN33  Electrically heated L-wire control port 2  Customized 
27  CN28 
TRANS  IN:  0-10V  valve 
powered  linear  transformer 
primary 
Customized