Midea AC Fan Coil Unit     
    51 
Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection,
where MFA is used to select the current circuit breakers and residual current operation breakers 
Table 10.4.1 
Communication  wire  between  indoor 
unit and wired controller 
  Table 10.4.2 
 
Wiring   
  See product wiring nameplate. 
  Check that the voltage and the frequency of the  power supply correspond to  220-240V single phase at 
50Hz/60Hz; that the available power is sufficient for the running the equipment; and that the supply cables 
are of adequate section for the maximum current which will be required. 
  Make sure that the power supply system complies with current national safety regulations.   
  Electrical connections must be made in accordance with the wiring diagrams supplied with the machine. For 
connection to  the  power  supply  network,  use  double-insulated  flexible  cable,  twin  pole  +  earth, section 
1.5mm2, type H05RN-F. 
  Pass the power supply cable through the slot beside the air filter. Use the cable clamp provided on the inner 
side of the panel to secure the power supply cable and the connecting cables, and strip only the length of 
cable needed to go into the connector block. In the event that the unit is mounted on a metal surface, earth 
connections must be made in compliance with local regulations. If the optional extra electric heating element 
is fitted, a separate power supply must be provided. Use double-insulated flexible cable, twin pole + earth, 
section 2.5mm2, type H05RN-F. 
Startup instructions 
Caution: 
Machine commissioning or the first startup must be carried out by skilled personnel qualified to work on this type 
of product. 
Before starting up, make sure that the installation and electrical connections have been carried out in accordance 
with the instructions in this manual. Also make sure that there are no unauthorized persons in the vicinity of the 
machine during these operations. 
 
Preliminary checks before startup 
  Before starting up the unit, make sure that: 
  The unit is positioned correctly; 
  The flow and return pipes of the water system are correctly connected; 
  The pipes are clean and free of air; 
 Rated current of appliance(A)
Nominal cross-sectional area (mm   )
>3
>6
>10
>16
>25
>32
>50
and
and
and
and
and
and
and
≤3
≤6
≤10
≤16
≤25
≤32
≤50
≤63
0.75
1
1.5
2.5
4
6
10
and
and
and
and
and
and
and
1
1.5
2.5
4
6
10
16
1
1
1.5
2.5
4
6
10
and
1 and
and
and
and
and
and
and
2.5
2.5
2.5
4
6
10
16
25
0.5 and 0.75
Flexible cords
Cable for fixed wiring
2