10.2 Troubleshooting
10.2.1 Open circuit or short circuit of temperature sensor diagnosis and solution(AS/E5/CS/oS/HS)
Error Code
AS/E5/CS/oS/HS
Malfunction decision
conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the
LED will display the failure.
Supposed causes
Wiring mistake
Faulty sensor
Faulty PCB
Troubleshooting:
Check the connection
between temperature
sensor and PCB.
Correct the connectionNo
Yes
Replace indoor main PCB
Measure the resistance
value of the sensor
Repalce the sensorNo
Yes