MCAC-RTSM-2015-01 60Hz R410a ClimaMaster Tropical Rooftop Package Unit
79
Belt section
For required to deflection belt 16 mm per meter of span
Small pulley diameter
(mm)
Newton
(N)
Kilogram-force
(kgf)
SPA
80 to132
25 to 35
2.5 to 3.6
SPB
140 to 224
45 to 65
4.6 to 6.6
NOTEThe belt which is too tight or too loose may generate noise and be harmful to the unit.
Dismantle the air filter.
Twist of screws and up the plate that is gets out.
Upon loose the filter-baffle-plate, the filter could be pulled out along the supporting slot.
5ton
Filter
Screw
Return I lateral plate assemblies
Extraction board of filter
Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust
accumulation is too heavy, please use soft brush and mild detergent to clean it and dry out in cool
place).
6.2ton and above