DM16‐01.01.27en RooftopClimaCreatorseries
76 Service manual
6. Electrical data
Model
Power Supply Compressor Eva.Fan Motor Con. Fan Motor
MCA TOCA MFA STC RNC IPT Qty RNC IPT Qty
RNC
(Each)
IPT
(Each)
Qty.
MRCT-062CWN1-R(C)
23.5 28.9 33.2 75 9.7 5.65 1 7.22 1.62 1 3.65 0.83 1
MRCT-075CWN1-R(C)
29.4 36.5 43.7 121.2 14.3 8.08 1 7.18 1.61 1 3.93 0.88 1
MRCT-085CWN1-R(C)
29.6 36.3 47.2 62 8.8 5.13 2 2.90 1.39 1 3.93 0.88 1
MRCT-100CWN1-R(C)
30.2 37.3 49.4 66 9.6 5.7 2 3.50 1.84 1 2.51 0.98 1
MRCT-125CWN1-R(C)
41.5 52.9 66.4 64+139 8.3+16.6 4.75+9.16 2 4.84 2.03 1 3.66 0.83 1
MRCT-150CWN1-R(C)
45.4 58.1 72.4 64+144 8.3+18.7 4.75+10.8 2 7.50 3.97 1 2.80 1.27 1
MRCT-175CWN1-R(C)
57.4 68.1 90.6 139 16.6 9.16 2 6.60 3.03 1 3.53 0.80 2
MRCT-200CWN1-R(C)
64.1 77.9 101.5 144 18.7 10.8 2 8.90 4.35 1 2.84 1.29 2
MRCT-250CWN1-R(C)
74.7 93.4 116.0 158 20.66 12.1 2 9.70 4.4 1 3.71 2.07 2
MRCT-300CWN1-R(C)
84.3 104.6 133.4 197 24.52 13.7 2 13.6 7.4 1 3.71 2.07 2
Notes:
MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps (A)
STC: Starting Current (A); RNC: Running Current (A); IPT: Input Power (kW); Qty: Quantity
Voltage imbalance between each phases should be ˂2%.