Troubleshooting   
248  Electrical Control 
c. Overload of current 
 
 
   
Yes
 
Yes
Replace the main PCB
 
No
 
Check if the operation condition is 
normal, especially the outdoor unit?
 
Check if the compressor is running 
Yes
Turn on the units and check if the 
problem remains
 
Yes
Check if the voltage of the power 
No
 
Replace the outdoor fan 
 
Yes
 
Check if the capillary is blocked
 
No
 
No
 
There is some air mixed inside the 
Evacuate the system and 
Regulate the power supply
 
Correct the operation condition
 
Replace the capillary
 
Check if the outdoor fan is defective
Replace the compressor
 
No