Electrical Control Function   
232  Electrical Control 
1. Electrical Control Function 
1.1 Abbreviation 
T1:    Indoor room temperature 
T2:    Evaporator coil temperature 
T3:    Condenser coil temperature 
T4:    Outdoor ambient temperature 
T5:    Compressor discharge temperature 
Ts:    Setting temperature 
 
1.2 Main Protection 
1.2.1 Compressor Restart Delay 
1.2.2  Sensor  protection  at  open  circuit  and 
breaking disconnection. 
1.2.3 Phase check function(for 3-phase models) 
If the phase sequence is detected wrong or lack of 
1 or 2 phase, the unit won’t start and there is error 
code displayed on outdoor PCB. 
1.2.4  Low  pressure  check  function(for  48-60K 
models) 
The low pressure switch should be always closed. If 
it  is  open,  the  system  will  stop  until  the  fault  is 
cleared.  Within  5  minutes  after  the  compressor 
starts  and  4  minutes  after  defrosting  ends,  low 
pressure switch won’t be checked. 
Note:  If  this  protection  occurs  3  times  within  20 
minutes,  it  won’t  recover  automatically  until  the 
main power is cut off. 
1.2.5  Over-current  protection(for  48-60K 
models) 
When compressor is running, if the current is over 
twice of the rated for 3 seconds, the compressor will 
stop  and  an  error  code  will  be  displayed  on  the 
outdoor  PCB.  If  the  current  becomes  normal,  the 
compressor will restart after 3 minutes.   
 
1.3 Operation Modes and Functions 
1.3.1 Fan mode 
  Outdoor  fan  and  compressor  cease 
operation. 
  Temperature setting function is disabled, and 
no preset temperature is displayed. 
  Indoor fan can be set to high, (
medium
), low, 
or auto. 
  Louver  operates  the  same  as  in  cooling 
mode. 
  Auto fan: 
For floor standing units: 
Auto fan will be controlled in line with cooling auto 
fan with temperature set to be 24°C. 
For other units: 
High
Low
Medium
 
1.3.2 Cooling Mode 
1.3.2.1 Compressor Running Guidelines   
Once  the  compressor  starts  up,  it  will  follow  the 
below rules: 
When  T1-Ts  is  higher  than  setting    value,  the 
compressor  and  outdoor  fan  cease  operation. 
When  T1-Ts  is  lower  than  setting    value,  the 
compressor and outdoor fan activate..   
T1-TS
On
Off
 
1.3.2.2 Outdoor Fan Running Guidelines 
For single-fan units: 
The outdoor fan will run following the compressor 
For double-fan units: 
The outdoor fans run depending on T3.