V6-i VRF 50/60Hz 
    91 
Part 
6 - Diagnosis and Troubleshooting
 
 Procedure 2.11.5
 
  Electronic expansion valve coil 
connection on main PCB is loose
1
 
Ensure the sensor is connected properly 
Electronic expansion valve coil has 
malfunctioned
2
 
 
Notes:   
1.  Electronic expansion valve coil connections are port CN70, CN71 and CN72 on the main PCB (labeled 18, 19 and 20, respectively, in Figure 5-2.1 in Part 5, 
2.1 “Ports”).   
2.  The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50Ω. If any of the resistances differ from the value, 
the EXV coil has malfunctioned. 
Figure 6-2.3: EXV coil wiring terminals