The number of connected indoor units is 6 and the maximum number of connected indoor units on the 14HP outdoor
unit is 64, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor units:
a) The sum of the indoor unit CIs is 454 and the CI of the 14HP outdoor unit (MV6-R400WV2GN1) is 400, so the
combination ratio is 454 / 400 = 113.5%.
b) Using the outdoor units’ cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-6.6 and 1-6.7.