V6R VRF 50/60Hz
18
Midea
V6R Series Engineering Data Book
Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units
Outdoor unit capacity
Sum of capacity indexes
Maximum
number of
connected
indoor units
kW
HP
Capacity
index
VRF indoor units
only
VRF indoor units
+ HT hydro
module
VRF indoor units
+ AHUs
VRF indoor units +
fresh air processing
units
33.5
12
335
167.5 to 435.5
167.5 to 670
167.5 to 368.5
167.5 to 335
64
40
14
400
200 to 520
200 to 800
200 to 440
200 to 400
45
16
450
225 to 585
225 to 900
225 to 495
225 to 450
50
18
500
250 to 650
250 to 1000
250 to 550
250 to 500
56
20
560
280 to 728
280 to 1120
280 to 616
280 to 560
61.5
22
615
307.5 to 799.5
307.5 to 1230
307.5 to 676.5
307.5 to 615
68
24
680
340 to 884
340 to 1360
340 to 748
340 to 680
73.5
26
735
367.5 to 955.5
367.5 to 1470
367.5 to 808.5
367.5 to 735
78.5
28
785
392.5 to 1020.5
392.5 to 1570
392.5 to 863.5
392.5 to 785
83.5
30
835
417.5 to 1085.5
417.5 to 1670
417.5 to 918.5
417.5 to 835
90
32
900
450 to 1170
450 to 1800
450 to 990
450 to 900
95
34
950
475 to 1235
475 to 1900
475 to 1045
475 to 950
The number of connected indoor units is 6 and the maximum number of connected indoor units on the 14HP outdoor
unit is 64, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor units:
a) The sum of the indoor unit CIs is 454 and the CI of the 14HP outdoor unit (MV6-R400WV2GN1) is 400, so the
combination ratio is 454 / 400 = 113.5%.
b) Using the outdoor units’ cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-6.6 and 1-6.7.
Table 1-6.6: Extract from Table 2-9.4 MV6-R400WV2GN1
cooling capacity
Table 1-6.7: Cooling capacity calculated by interpolation
CR
Outdoor
air
temp.
C DB)
Indoor air temp.
C DB / °C WB)
CR
Outdoor
air
temp.
C DB)
Indoor air temp.
C DB / °C WB)
25.8 / 18.0
25.8 / 18.0
TC
PI
TC
PI
kW
kW
kW
kW
120%
31
48.00
11.02
120%
33
45.73
10.99
33
45.73
10.99
35
44.05
11.00
B = 41.2
1
110%
31
40.62
8.74
110%
33
40.62
9.38
33
40.62
9.38
35
40.62
10.17
Notes:
1. 40.62 + (45.73 40.62) × (113.5 110) / (120 110) =
41.2.

Other manuals for Midea MV6-R450WV2GN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV6-R450WV2GN1 and is the answer not in the manual?

Midea MV6-R450WV2GN1 Specifications

General IconGeneral
BrandMidea
ModelMV6-R450WV2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals