V6R Series Engineering Data Book
7 Electrical Characteristics
Table 2-7.1: Outdoor unit electrical characteristics
Model
Power Supply
1
Compressor
OFM
Capacity
Modules
Hz
Volts
Min.
Max.
MCA
2
TOCA
3
MFA
4
MSC
5
RLA
6
kW
FLA
volts
volts
8HP
50/60
380~415
342
456
18
21.3
20
/
12.2
0.92
1.3
10HP
50/60
380~415
342
456
22
25.5
25
/
16.5
0.92
1.5
12HP
50/60
380~415
342
456
24
27.7
25
/
17.2
0.92
1.7
14HP
50/60
380~415
342
456
28
31.7
30
/
20.1
0.92×2
1.7
16HP
50/60
380~415
342
456
34
37.9
35
/
24.5
0.92×2
1.9
18HP
50/60
380~415
342
456
36
40.2
40
/
29.7
0.92×2
2.2
20HP
50/60
380~415
342
456
36
40.2
40
/
29.7
0.92×2
2.2
22HP
10HP
12HP
50/60
380~415
342
456
46
42.6
25+25
/
16.5+17.2
0.92×2
3.2
24HP
10HP
14HP
50/60
380~415
342
456
50
53.2
25+30
/
16.5+20.1
0.92×3
3.2
26HP
12HP
14HP
50/60
380~415
342
456
52
57.2
25+30
/
17.2+20.1
0.92×3
3.4
28HP
12HP
16HP
50/60
380~415
342
456
58
59.4
25+35
/
17.2+24.5
0.92×3
3.9
30HP
12HP
18HP
50/60
380~415
342
456
60
65.6
25+40
/
17.2+29.7
0.92×3
3.9
32HP
16HP
16HP
16HP
16HP
50/60
380~415
342
456
68
67.9
35+35
/
24.5×2
0.92×4
3.8
34HP
16HP
16HP
16HP
18HP
50/60
380~415
342
456
70
75.8
35+40
/
24.5+29.7
0.92×4
4.1
36HP
18HP
18HP
50/60
380~415
342
456
72
78.1
40+40
/
29.7×2
0.92×4
4.4
38HP
18HP
20HP
50/60
380~415
342
456
72
80.4
40+40
/
29.7×2
0.92×4
4.4
40HP
20HP
20HP
50/60
380~415
342
456
72
80.4
40+40
/
29.7×2
0.92×4
4.4
42HP
12HP
14HP
16HP
50/60
380~415
342
456
86
80.4
25+30+35
/
17.2+20.1+24.5
0.92×5
5.3
44HP
12HP
16HP
16HP
50/60
380~415
342
456
92
87.1
25+35+35
/
17.2+24.5×2
0.92×5
5.5
46HP
14HP
16HP
16HP
50/60
380~415
342
456
96
93.3
30+35+35
/
20.1+24.5×2
0.92×6
5.5
48HP
16HP
16HP
16HP
50/60
380~415
342
456
102
97.3
35+35+35
/
24.5×3
0.92×6
5.7
50HP
16HP
16HP
18HP
50/60
380~415
342
456
104
103.5
35+40+40
/
24.5×2+29.7
0.92×6
6
52HP
16HP
18HP
18HP
50/60
380~415
342
456
106
107.5
35+40+40
/
24.5+29.7×2
0.92×6
6.3
54HP
18HP
18HP
18HP
50/60
380~415
342
456
108
113.7
40+40+40
/
29.7×3
0.92×6
6.6
56HP
18HP
18HP
20HP
50/60
380~415
342
456
108
116
40+40+40
/
29.7×3
0.92×6
6.6
58HP
18HP
20HP
20HP
50/60
380~415
342
456
108
118.3
40+40+40
/
29.7×3
0.92×6
6.6
60HP
20HP
20HP
20HP
50/60
380~415
342
456
108
120.6
40+40+40
/
29.7×3
0.92×6
6.6
Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA: Rated Load Amps; FLA: Full
Load Amps
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage
variation between phases is 2%.
2. Select wire size based on the value of MCA.
3. TOCA indicates the total overcurrent amps value of each OC set.
4. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5. MSC indicates the maximum current on compressor start-up in amps.
6. RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.

Other manuals for Midea MV6-R450WV2GN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV6-R450WV2GN1 and is the answer not in the manual?

Midea MV6-R450WV2GN1 Specifications

General IconGeneral
BrandMidea
ModelMV6-R450WV2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals