VC Pro VRF 50/60Hz
103
Part 2 - Outdoor Unit Engineering Data
Table 2-8.11: 28HP cooling capacity (continued)
Combinatio
n (%)
(Capacity
index)
Outdoor
temperatur
e (°C DB)
Indoor temperature(°C DB/WB)
DB:20.8,WB:1
4
DB:23.3,WB:1
6
DB:25.8,WB:1
8
DB:27,WB:19
DB:28.2,WB:2
0
DB:30.7,WB:2
2
DB:32,WB:24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-5
26.49
4.22
31.68
4.88
36.73
5.61
39.25
5.87
41.77
6.19
46.82
7.04
52.15
7.59
-2
26.49
4.25
31.68
4.98
36.73
5.67
39.25
5.95
41.77
6.31
46.82
7.14
52.15
7.69
0
26.49
4.32
31.68
5.06
36.73
5.77
39.25
6.03
41.77
6.38
46.82
7.26
52.15
7.82
2
26.49
4.38
31.68
5.12
36.73
5.87
39.25
6.12
41.77
6.49
46.82
7.29
52.15
7.98
4
26.49
4.43
31.68
5.21
36.73
5.93
39.25
6.19
41.77
6.62
46.82
7.47
52.15
8.18
6
26.49
4.51
31.68
5.29
36.73
6.02
39.25
6.34
41.77
6.74
46.82
7.58
52.15
8.42
8
26.49
4.62
31.68
5.39
36.73
6.12
39.25
6.48
41.77
6.83
46.82
7.71
52.15
8.69
10
26.49
4.71
31.68
5.45
36.73
6.22
39.25
6.58
41.77
7.03
46.82
7.91
52.15
8.82
12
26.49
4.75
31.68
5.52
36.73
6.33
39.25
6.71
41.77
7.17
46.82
8.05
52.15
8.96
14
26.49
4.81
31.68
5.59
36.73
6.40
39.25
6.85
41.77
7.28
46.82
8.19
52.15
9.14
16
26.49
4.88
31.68
5.66
36.73
6.50
39.25
6.96
41.77
7.38
46.82
8.33
52.15
9.28
18
26.49
4.96
31.68
5.76
36.73
6.61
39.25
7.06
41.77
7.52
46.82
8.47
52.15
9.45
20
26.49
5.03
31.68
5.83
36.73
6.71
39.25
7.17
41.77
7.66
46.82
8.61
52.15
9.63
21
26.49
5.06
31.68
5.90
36.73
6.78
39.25
7.24
41.77
7.73
46.82
8.72
52.15
9.74
23
26.49
5.13
31.68
5.97
36.73
6.89
39.25
7.38
41.77
7.87
46.82
8.86
52.15
9.95
25
26.49
5.20
31.68
6.08
36.73
7.03
39.25
7.52
41.77
8.12
46.82
9.31
52.15
10.61
27
26.49
5.31
31.68
6.33
36.73
7.42
39.25
8.01
41.77
8.61
46.82
9.91
52.15
11.32
29
26.49
5.59
31.68
6.68
36.73
7.87
39.25
8.51
41.77
9.17
46.82
10.54
52.15
12.05
31
26.49
5.90
31.68
7.06
36.73
8.33
39.25
9.03
41.77
9.74
46.82
11.21
52.15
12.83
33
26.49
6.26
31.68
7.49
36.73
8.86
39.25
9.56
41.77
10.33
46.82
11.91
52.15
13.64
35
26.49
6.61
31.68
7.91
36.73
9.35
39.25
10.12
41.77
10.93
46.82
12.65
52.15
14.48
37
26.49
6.96
31.68
8.36
36.73
9.91
39.25
10.72
41.77
11.60
46.82
13.43
52.15
15.39
39
26.49
7.35
31.68
8.82
36.73
10.47
39.25
11.35
41.77
12.30
46.82
14.23
52.15
16.34
41
26.49
7.65
31.68
9.20
36.73
10.85
39.25
11.88
41.77
12.83
46.82
14.99
52.15
17.10
43
26.03
8.01
31.13
9.66
36.09
11.03
38.57
12.19
41.05
12.92
46.01
15.47
51.24
17.54
46
26.03
8.19
31.13
9.90
36.09
11.77
38.57
13.13
41.05
13.47
46.01
16.96
51.24
19.03
48
26.03
8.35
31.13
10.14
36.09
12.42
38.57
14.01
41.05
14.11
46.01
18.29
51.24
20.47
50
25.72
8.41
30.93
10.23
35.83
12.51
38.26
14.04
40.73
14.14
45.62
18.40
50.79
20.59
52
25.41
8.46
30.31
10.28
35.21
12.56
37.64
14.09
40.11
14.19
45.01
18.49
49.90
20.64
55
25.11
8.51
30.00
10.37
34.59
12.66
37.02
14.19
39.49
14.28
44.08
18.63
49.29
20.78
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
Shaded cells indicate rating condition.